
Basic Electrical Inspection Guide
Standards of Practice
The International Standards of Practice for inspecting the electrical system is located at www.nachi.org/sop.
​
Free, Online Course
To learn more, take InterNACHI's free, online How to Perform Residential Electrical Inspections Course.
Weatherhead
​
Observation

Not minimum 13' height (NEC) above floor.
​
Observation

No bushing (phenolic insulator).
​
Observation

Inadequate drip loop.
​
Observation

Improper splices.
Illegal line-side tap (inside soffit).
Mast
​
Observation

Inadequate attachment to wall.
​
Observation

The mast is electrical metallic tubing (EMT) which is NOT an acceptable material. The mast should be of:
-
Intermediate metal conduit (IMC); or
-
Galvanized rigid conduit (GRC). Samples of each are attached to the wall.
Meter
Observation

The amperage rating of the 3/0 (225-amp) copper service entrance conductors exceeds the amperage rating of the electric meter socket enclosure (135 amps) as viewed on the meter label.
​
Observation

The bonding bushing conductor is in contact with phase lug.
​
Note:
Also attached to the wall is a section of polyvinyl chloride (PVC) conduit that is NOT acceptable as electrical mast material.
​
Electrical Panels-Panel #1 (Service Panel)
​
Observation

Description: GE 200-amp Main Breaker Panel with a 200-amp main disconnect (no other breakers).
Observation

Observation

Panel/components are not connected to a service grounding system (SGS) SGSs include:
-
Grounding electrode conductor (GEC);
-
Grounding electrode (examples: driven rod(s), concrete encased, grounding ring/plate, water pipe where acceptable).
​
Observation

Main lugs are double tapped to feed panel #2.
​
Observation

Panel/components are not connected to a service grounding system (SGS).
Distribution (sub-) Panel
​
Observation

The 200-amp service panel is inadequate for feeding the 200-amp.
​
Observation

Observation

A main bonding jumper connecting the neutral and grounding bus bars should be installed in the service panel only (point of first disconnect).
​
Observation

No conductors attached to bonding bushings.
​
Observation

Main feed conductor over-stripped (1" max. according to label).
​
Observation

A cable connector should be installed to protect the conductor insulation from abrasion.
​
CONDITIONS NOT DEFECTS:
​
Observation

The amperage rating of the 3/0 (225-amp) copper feeders exceeds the 200-amp maximum rating of the load center.
​
This is acceptable as long as the amperage rating of the main disconnect does not exceed the amperage rating of load center.
​
Observation

Multiple grounds under the same screw.
​
Observation

Vinyl insulation extends several inches into the panel.
​
Observation

Pig-tailed breaker.
Distribution (sub-) Panel
GE 100-amp Main Breaker load center with no main disconnect. Backfed by 125-amp breaker. Circuit breakers are installed.
​
Observation

Unfilled holes.
​
Observation

Missing cable connector.
​
Observation

Deadfront cover attached with improper screws.
Sharp, course-thread screws can cut conductor insulation potentially causing a dangerous arc flash.
Observation

Deadfront cover missing filler plates (twistouts).
​
Observation

The amperage rating of the 125-amp backfeed breaker exceeds the 100-amp maximum amperage rating of both the #4 copper feeders and the load center.
The 125-amp backfeed breaker has no retaining device.
​
Observation

No bonding bushing.
​
Wherever feeders enter or leave a load center through concentric knockouts, a bonding bushing must be installed to ensure electrical continuity of the bonding/equipment grounding system. Bonding bushings should be connected to the neutral bus bar.
​
Observation

No insulated bushing is installed to protect feeders against abrasion where they enter the load center.
Observation

Observation

Multiple 20-amp breakers are connected to 14-gauge conductors. 20-amp breakers should be connected to 12-gauge conductors.
​
Observation

The GFCI breaker is connected to the grounding bus bar, not the neutral bus bar.
​
Observation

Multiple neutral conductors under the same screw in the neutral bus bar.
This is wrong because it complicates isolating the neutral for one of the circuits involved.
​
Observation

Pig-tailed neutrals.
Again, this is wrong because it complicates isolating the neutral for one of the circuits involved.
Observation

Neutral conductor.
​
Observation

In order to complete their insertion into the 125-amp breaker (lower right corner) the #1 (150-amp) copper conductors had strands cut away.
​
Cutting strands reduces the amperage rating of a conductor. 37. Unfilled Knockout.
​
Observation

Unfilled Knockout.
​
Observation

Grounding conductor on the neutral bus bar.
First Detached Structure Electrical Panel
Square D 125-amp load center, backfed by 125-amp breaker.​
Grounding conductors of different gauges under the same screw. The 125-amp backfeed breaker has no retaining device. Neutral and grounding bus bars are not isolated from each other.
​
Second Detached Structure Electrical Panel
Neutral and grounding bus bars are not isolated from each other.
​
Observation

