top of page
internachi home inspection school

Basic Electrical Inspection Guide

Standards of Practice

The International Standards of Practice for inspecting the electrical system is located at www.nachi.org/sop.

​

Free, Online Course

To learn more, take InterNACHI's free, online How to Perform Residential Electrical Inspections Course.

Weatherhead

​

Observation

100_5912

Not minimum 13' height (NEC) above floor.

​

Observation

100_5913-1024x768

No bushing (phenolic insulator).

​

Observation

100_5915-1024x768

Inadequate drip loop.

​

Observation

100_5917-1024x768

Improper splices.

Illegal line-side tap (inside soffit).

Mast

​

Observation

100_5919-1024x768

Inadequate attachment to wall.

​

Observation

100_5923-1024x768

The mast is electrical metallic tubing (EMT) which is NOT an acceptable material. The mast should be of:

  1. Intermediate metal conduit (IMC); or

  2. Galvanized rigid conduit (GRC). Samples of each are attached to the wall.

Meter

 

Observation

100_5921-1024x768

The amperage rating of the 3/0 (225-amp) copper service entrance conductors exceeds the amperage rating of the electric meter socket enclosure (135 amps) as viewed on the meter label.

​

Observation

100_5926-1024x768

The bonding bushing conductor is in contact with phase lug.

​

Note:

Also attached to the wall is a section of polyvinyl chloride (PVC) conduit that is NOT acceptable as electrical mast material.

​

Electrical Panels-Panel #1 (Service Panel)

​

Observation

100_5924-1024x768

Description: GE 200-amp Main Breaker Panel with a 200-amp main disconnect (no other breakers).

 

Observation

100_5999-1024x768

Observation

100_6000-1024x768

Panel/components are not connected to a service grounding system (SGS) SGSs include:

  1. Grounding electrode conductor (GEC);

  2. Grounding electrode (examples: driven rod(s), concrete encased, grounding ring/plate, water pipe where acceptable).

​

Observation

100_5925-1024x768

Main lugs are double tapped to feed panel #2.

​

Observation

100_5926-1-1024x768

Panel/components are not connected to a service grounding system (SGS).

Distribution (sub-) Panel

​

Observation

100_5928-1024x768

The 200-amp service panel is inadequate for feeding the 200-amp.

​

Observation

100_5930-1024x768

Observation

100_5967-1024x768

A main bonding jumper connecting the neutral and grounding bus bars should be installed in the service panel only (point of first disconnect).

​

Observation

100_5933-1024x768

No conductors attached to bonding bushings.

​

Observation

basic-electrical-0819-1

Main feed conductor over-stripped (1" max. according to label).

​

Observation

100_5936-1024x768

A cable connector should be installed to protect the conductor insulation from abrasion.

​

CONDITIONS NOT DEFECTS:

​

Observation

100_5941-1024x768

The amperage rating of the 3/0 (225-amp) copper feeders exceeds the 200-amp maximum rating of the load center.

​

This is acceptable as long as the amperage rating of the main disconnect does not exceed the amperage rating of load center.

​

Observation

100_5937-1024x768

Multiple grounds under the same screw.

​

Observation

100_5939-1024x768

Vinyl insulation extends several inches into the panel.

​

Observation

pig-tailed_breaker

Pig-tailed breaker.

Distribution (sub-) Panel

 

GE 100-amp Main Breaker load center with no main disconnect. Backfed by 125-amp breaker. Circuit breakers are installed.

​

Observation

100_5959-1024x768

Unfilled holes.

​

Observation

100_5944-1024x768

Missing cable connector.

​

Observation

100_5942-1024x768

Deadfront cover attached with improper screws.

Sharp, course-thread screws can cut conductor insulation potentially causing a dangerous arc flash.

 

Observation

100_5943-1024x768

Deadfront cover missing filler plates (twistouts).

​

Observation

100_5945-1024x768

The amperage rating of the 125-amp backfeed breaker exceeds the 100-amp maximum amperage rating of both the #4 copper feeders and the load center.

The 125-amp backfeed breaker has no retaining device.

​

Observation

100_5946-1024x768

No bonding bushing.

​

Wherever feeders enter or leave a load center through concentric knockouts, a bonding bushing must be installed to ensure electrical continuity of the bonding/equipment grounding system. Bonding bushings should be connected to the neutral bus bar.

​

Observation

100_5944-1024x768

No insulated bushing is installed to protect feeders against abrasion where they enter the load center.

 

Observation

100_5949-1024x768

Observation

100_5962-1024x768

Multiple 20-amp breakers are connected to 14-gauge conductors. 20-amp breakers should be connected to 12-gauge conductors.

​

Observation

100_5950-1024x768

The GFCI breaker is connected to the grounding bus bar, not the neutral bus bar.

​

Observation

100_5938-1024x768

Multiple neutral conductors under the same screw in the neutral bus bar.

This is wrong because it complicates isolating the neutral for one of the circuits involved.

​

Observation

100_5953-1024x768

Pig-tailed neutrals.

Again, this is wrong because it complicates isolating the neutral for one of the circuits involved.

 

Observation

100_5988-1024x768

Neutral conductor.

​

Observation

100_5934-1024x768

In order to complete their insertion into the 125-amp breaker (lower right corner) the #1 (150-amp) copper conductors had strands cut away.

​

Cutting strands reduces the amperage rating of a conductor. 37. Unfilled Knockout.

​

Observation

Electrical

Unfilled Knockout.

​

Observation

basic-electrical-0819-1-1

Grounding conductor on the neutral bus bar.

First Detached Structure Electrical Panel

 

Square D 125-amp load center, backfed by 125-amp breaker.​

Grounding conductors of different gauges under the same screw. The 125-amp backfeed breaker has no retaining device. Neutral and grounding bus bars are not isolated from each other.

​

Second Detached Structure Electrical Panel

Neutral and grounding bus bars are not isolated from each other.

​

Observation

100_5963-1024x768

Neutral and grounding bus bars are not isolated from each other.

bottom of page